Cooler Flow Range:
Chiller ratings and performance data pertain to cooling temperature rise of 10 (-
12.4℃). Chillers maybe suitable for operation in a range from 5.4 to 14.5 (-15~-9.9
℃ )temperature rise without adjustment, provided flow limits are not exceeded. High
flow rate is limited by pressure drop that can be tolerated ( for any high flow rate value
larger than values in performance tables, please refer to GREE factory).
Minimum Cooler Flow: Minimum cooler flow will be based on the maximum permissible AT
across the cooler 14.5 (-9.9℃).
℉
℉
℉
Maximum Cooler Flow
It Will be based on Minimum permissible AT across the cooler 5.4 (-15℃).℉
Cooler protection
A protection against low ambient freeze-up is required for ambient temperatures below
32 (0℃ ) . Protection should be in the form of: Inhibited ethylene glycol or any other
suitable glycol .
℉
Condenser Airflow
Any restrictions on units fan airflow will affect unit capacity, condenser head pres-sure, and
compressor power input. Such restrictions (i.e. not providing vertical clear-ance or lateral
clearance, insufficient unit-to-unit clearance ) will cause warm air rec-irclation or coil
starvation. Minimum required operational and maintenance clearan-ces around the unit
are shown in the figure below.